Summary

Subject of the contract: Project proposal for energy retrofitting measures for the real estate portfolio of a municipality in Northern Italy, in response to the public notice calling for expressions of interest in a public-private partnership pursuant to Article 193 of Legislative Decree No. 36 of 2023.

Objective of the contract: To identify an optimal set of energy retrofit measures for the buildings within the project scope that are owned by the municipality.

Key Information

Client Name: Consortium of leading national operators in the energy services and facility management sectors

Project Name: Feasibility Study for the Energy Retrofit of a Municipality’s Real Estate Portfolio in Northern Italy

Project period: Second half of 2025

Total project cost: Over €90,000,000

Properties involved: The total real estate portfolio consists of nearly 300 properties, covering a total area of over 420,000 m2

Brief description of the planned activities

Analysis of Municipal Assets and Reconstruction of Energy Baselines

As part of the project, a thorough analysis was conducted of the documentation provided by the client andthe municipal administration, including:

  • photos,
  • reports and surveys from site inspections,
  • energy consumption,
  • floor plans,
  • Energy Performance Certificates.

The analysis made it possible to accurately assess the current condition of each building and to establish reliable energy baselines— normalized based on degree-days and system operating hours — thereby identifying critical issues and opportunities for action.

Proposed Measures for the Energy Retrofit of Municipal Properties

The proposed measures were organized into three levels of energy retrofitting: comprehensive, extensive, and basic.

The solutions identified addressed the areas described below.

Improving the Energy Efficiency of Air Conditioning Systems

Energy-efficiency improvements to air-conditioning systems, such as:

  • replacing existing heat generators with various types of electric heat pumps (air-to-water, VRF air-to-air, and geothermal) or with“factory-made” hybrid systems,
  • connection to the district heating network,
  • replacement of outdated refrigeration units with new, more efficient ones,
  • installation of a heat pump water heater;

Distribution

and

Outlet

Systems for

Heating Systems

For the distribution and outlet systems

of

heating systems, the following measures have been proposed:

  • installation of inverter-driven circulators,
  • Renovation of the insulation in the heating plant and the secondary distribution system,
  • Replacement of emission terminals with fan coil units, radiant panels, and VRF indoor units.

Mechanical Ventilation and Heat Recovery

For mechanical ventilation, measures such asthe installation of heat recovery units and inverter-driven fans on the air handling units and the installation of localized controlled mechanical ventilation systems.

Work on Electrical Systems

Work on electrical systems, such as replacing lighting with energy-efficient LED technology in combination withlighting control systems (LCS).

Photovoltaic and Solar Thermal Systems

The project involved the installation of renewable energy systems —specifically photovoltaic systems with a total capacity of approximately 3.5 MWp and solar thermal systems.

Smart Terminal Control and BACS Remote Monitoring

Smart control of heating and cooling terminals and remote monitoring played an important role: plans called forthe installation of more than 16,000 room-temperature control devices in most of the buildings, including:

  • wireless smart valve on radiators,
  • smart regulators with pressure – independent balancing valves on the fan coils,
  • electrothermal heads with dynamic collectors on radiant panels,
  • ambient temperature and humidity probes (integrated with CO₂ measurement in nZEB buildings).

The devices, connected via radio (LoRaWAN) or by cable to controllers installed in each boiler room and on each floor, are integrated into a BACS system for remote control and monitoring system covering approximately 9,000 controlled points.

The power output from each terminal thus adapts in real time to free energy sources, such as solarradiation and the presence of people, ensuring compliance with Automation Class B as defined by UNI EN ISO 52120-1.

nZEB Buildings and Projected Reductions in Energy Consumption and Emissions

Overall, the feasibility study for the energy retrofit of the real estate portfolio called for work on nearly all of the buildings, 33 of which were converted into nZEBs, resulting in a reduction in total energy consumption of more than 30% in TOE and well over 3,000 metric tons of CO2 avoided.

Energy Efficiency Retrofit Projects with Enertech Solution

In this project, Enertech Solution analyzed the current state of the city’s building stock and defined the proposed energy retrofit measures.

Discover Enertech Solution’s other projects or contact the team to discuss the specific needs of your buildings.

Do you need counseling?

Fill out the form, and we will get back to you as soon as possible.

Contact us